O/C و E/F زمان عملکرد رله های : ................................................................................ Company or Region Name = ZREC Group or Checker Name = Group_1 Substation Name = Test_230kV_OK Voltage = 230 / 63 kV Calculation date & time = 2016 / 2 / 8 on Monday at 16:34:4 S [Power Transformer(s) apparent power] = 160 MVA Sbase = 100 MVA Transformer(s) Type = Autotransformer ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: A1 TMS = 0.05 Is (Primary) = 320 A Characteristic: SI TR(A1) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 11510.35 A] = 0.094 sec TR(A1) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 4133.1 A] = 0.133 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: A1 TMS = 1 Is (Primary)= 80 A Characteristic: SI TR(A1) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 2327.73 A] = 2.008 sec TR(A1) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 1125.37 A] = 2.578 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: A2 TMS = 0.075 Is (Primary) = 480 A Characteristic: SI TR(A2) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 11510.35 A] = 0.16 sec TR(A2) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 4133.1 A] = 0.239 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: A2 TMS = 0.25 Is (Primary)= 80 A Characteristic: SI TR(A2) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 2327.73 A] = 0.502 sec TR(A2) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 1125.37 A] = 0.645 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: A3 TMS = 0.25 Is (Primary) = 520 A Characteristic: SI TR(A3) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 11510.35 A] = 0.548 sec TR(A3) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 4133.1 A] = 0.827 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: A3 TMS = 1 Is (Primary)= 80 A Characteristic: SI TR(A3) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 2327.73 A] = 2.008 sec TR(A3) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 1125.37 A] = 2.578 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: A4 TMS = 0.1 Is (Primary) = 520 A Characteristic: SI TR(A4) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 11510.35 A] = 0.219 sec TR(A4) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 4133.1 A] = 0.331 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: A4 TMS = 1 Is (Primary)= 40 A Characteristic: SI TR(A4) for [Fault current (Max) at 63 kV side Buscoupler with Parallel Trans. = 2327.73 A] = 1.653 sec TR(A4) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 1125.37 A] = 2.028 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Bus_LV_1 TMS = 0.25 Is (Primary) = 1600 A Characteristic: SI TR(Bus_LV_1) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 7157.31 A] = 1.151 sec TR(Bus_LV_1) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 2758.45 A] = 3.196 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: Bus_LV_1 TMS = 0.775 Is (Primary)= 200 A Characteristic: SI TR(Bus_LV_1) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 1187.69 A] = 2.991 sec TR(Bus_LV_1) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 1044.73 A] = 3.228 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Incoming_1 TMS = 0.325 Is (Primary) = 1800 A Characteristic: SI TR(Incoming_1) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 7157.31 A] = 1.625 sec TR(Incoming_1) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 2758.45 A] = 5.307 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Incoming_2 TMS = 0.325 Is (Primary) = 1800 A Characteristic: SI TR(Incoming_2) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 7157.31 A] = 1.625 sec TR(Incoming_2) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 2758.45 A] = 5.307 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Trans_1 TMS = 0.35 Is (Primary) = 2125 A Characteristic: SI TR(Trans_1) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 7157.31 A] = 1.993 sec TR(Trans_1) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 2758.45 A] = 9.366 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: Trans_1 TMS = 1 Is (Primary)= 60 A Characteristic: SI TR(Trans_1) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 1187.69 A] = 2.275 sec TR(Trans_1) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 1044.73 A] = 2.381 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Trans_2 TMS = 0.35 Is (Primary) = 2125 A Characteristic: SI TR(Trans_2) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 7157.31 A] = 1.993 sec TR(Trans_2) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 2758.45 A] = 9.366 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: Trans_2 TMS = 1 Is (Primary)= 60 A Characteristic: SI TR(Trans_2) for [Fault current (Max) at 63 kV side Buscoupler with single Trans. = 1187.69 A] = 2.275 sec TR(Trans_2) for [Fault current (Min) at 63 kV side Buscoupler with single Trans. = 1044.73 A] = 2.381 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: HV_1 TMS = 0.45 Is (Primary) = 510 A Characteristic: SI TR(HV_1) for [Fault current (Max) at 230 kV side = 7997.56 A] = 1.113 sec TR(HV_1) for [Fault current (Min) at 230 kV side = 2276.77 A] = 2.074 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: HV_1 TMS = 0.05 Is (Primary)= 90 A Characteristic: SI TR(HV_1) for [Fault current (Max) at 230 kV side = 8138.13 A] = 0.074 sec TR(HV_1) for [Fault current (Min) at 230 kV side = 2735.89 A] = 0.099 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: HV_2 TMS = 0.45 Is (Primary) = 510 A Characteristic: SI TR(HV_2) for [Fault current (Max) at 230 kV side = 7997.56 A] = 1.113 sec TR(HV_2) for [Fault current (Min) at 230 kV side = 2276.77 A] = 2.074 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: HV_2 TMS = 0.05 Is (Primary)= 90 A Characteristic: SI TR(HV_2) for [Fault current (Max) at 230 kV side = 8138.13 A] = 0.074 sec TR(HV_2) for [Fault current (Min) at 230 kV side = 2735.89 A] = 0.099 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: LV_Neutral_2 TMS = 0 Is (Primary)= 0 A Characteristic: SI ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Abhar TMS = 0.05 Is (Primary) = 540 A Characteristic: SI Direction: Line side TR(Abhar) for [IF1 = 2742.41 A] = 0.212 sec TR(Abhar) for [IF2 = 2138.71 A] = 0.251 sec TR(Abhar) for [IF5 = 1255.11 A] = 0.411 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: Abhar TMS = 0.25 Is (Primary)= 360 A Characteristic: SI Direction: Line side TR(Abhar) for [Ie1 = 6195.22 A] = 0.598 sec TR(Abhar) for [Ie2 = 3012.26 A] = 0.806 sec TR(Abhar) for [Ie5 = 1255.11 A] = 1.384 sec TR(Abhar) for [Ie6 = 978.99 A] = 1.732 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Eshragh TMS = 0.475 Is (Primary) = 540 A Characteristic: SI Direction: Busbar side This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF1(Abhar) = 2742.41 A] = 0.212 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF1(Boein Zahra) = 5509.93 A] = 1.399 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF2(Abhar) = 2138.71 A] = 0.251 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF2(Boein Zahra) = 2008.17 A] = 2.498 sec TR(Eshragh) for [IF3 = 1757.15 A] = 2.785 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF3(Abhar) = 1782.26 A] = 0.29 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF3(Boein Zahra) = 1757.15 A] = 2.785 sec TR(Eshragh) for [IF4 = 1506.13 A] = 3.208 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF4(Abhar) = 1506.13 A] = 0.338 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF4(Boein Zahra) = 1506.13 A] = 3.208 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF5(Abhar) = 1255.11 A] = 0.411 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF5(Boein Zahra) = 1255.11 A] = 3.909 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF6(Abhar) = 0 A] = -0.007 sec This Relay Looks to other Lines' Faults: TR(Eshragh) for [IF6(Boein Zahra) = 2008.17 A] = 2.498 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: Eshragh TMS = 0.4 Is (Primary)= 420 A Characteristic: SI Direction: Busbar side TR(Eshragh) for [Ie3 = 6195.22 A] = 1.013 sec TR(Eshragh) for [Ie4 = 3012.26 A] = 1.393 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Boein Zahra TMS = 0.475 Is (Primary) = 540 A Characteristic: SI Direction: NonDirectional TR(Boein Zahra) for [IF1 = 5509.93 A] = 1.399 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF1(Abhar) = 2742.41 A] = 0.212 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF1(Eshragh) = 5509.93 A] = 1.399 sec TR(Boein Zahra) for [IF2 = 2008.17 A] = 2.498 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF2(Abhar) = 2138.71 A] = 0.251 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF2(Eshragh) = 2008.17 A] = 2.498 sec TR(Boein Zahra) for [IF3 = 1757.15 A] = 2.785 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF3(Abhar) = 1782.26 A] = 0.29 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF3(Eshragh) = 1757.15 A] = 2.785 sec TR(Boein Zahra) for [IF4 = 1506.13 A] = 3.208 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF4(Abhar) = 1506.13 A] = 0.338 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF4(Eshragh) = 1506.13 A] = 3.208 sec TR(Boein Zahra) for [IF5 = 1255.11 A] = 3.909 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF5(Abhar) = 1255.11 A] = 0.411 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF5(Eshragh) = 1255.11 A] = 3.909 sec TR(Boein Zahra) for [IF6 = 2008.17 A] = 2.498 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF6(Abhar) = 0 A] = -0.007 sec This Relay Looks to other Lines' Faults: TR(Boein Zahra) for [IF6(Eshragh) = 2008.17 A] = 2.498 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: Boein Zahra TMS = 0.45 Is (Primary)= 420 A Characteristic: SI Direction: NonDirectional TR(Boein Zahra) for [Ie1 = 3321.02 A] = 1.492 sec TR(Boein Zahra) for [Ie2 = 2018.22 A] = 1.975 sec TR(Boein Zahra) for [Ie3 = 6195.22 A] = 1.139 sec TR(Boein Zahra) for [Ie4 = 3012.26 A] = 1.568 sec TR(Boein Zahra) for [Ie5 = 953.88 A] = 3.809 sec TR(Boein Zahra) for [Ie6 = 903.68 A] = 4.08 sec ---------------------------------------------- ----------------- O/C ------------------ Feeder Name: Bus_HV TMS = 1 Is (Primary) = 1000 A Characteristic: SI TR(Bus_HV) for [IP3Min = 1832.86 A] = 11.484 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: Bus_HV TMS = 1 Is (Primary)= 400 A Characteristic: SI TR(Bus_HV) for [Ie3Min = 6415 A] = 2.453 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: HV_Neutral_1 TMS = 0.625 Is (Primary)= 120 A Characteristic: SI TR(HV_Neutral_1) for [Ie3Min = 916.43 A] = 2.109 sec ---------------------------------------------- ----------------- E/F ------------------ Feeder Name: HV_Neutral_2 TMS = 0.425 Is (Primary)= 120 A Characteristic: SI TR(HV_Neutral_2) for [Ie3Min = 916.43 A] = 1.434 sec